Loading...

SINGLE LOOP ADDRESSABLE FIRE ALARM CONTROL PANEL

The purpose of the SEC1000 Fire Alarm Control Panel (FACP) is to monitor input signals, give indications and possibly activate outputs as programmed. It is designed to comply with EN 54-2 with qualities of simple installation, operation and easy maintenance.

  • FEATURES:
    • Up to 120 addresses on one loop.

    • The loop supports class A and Class B types.

    • An easy to read, 4.3"color screen LCD with a resolution of 480×272.

    • Zone indicators for 16 zones gives a quick indication of the location of an alarm.

    • An independently programmable conventional sounder circuit output.

    • Integral power supply and battery.

    • Flexible and intuitive cause and effect programming on front panel.

    • Zone test, point test and module start/stop testing facilitate the commissioning.

    • Hierarchy management with three access levels.

    • Anti-tamper protection by a key lock.

    • CAN bus for interconnection of up to 20 FACPs.

Model: SEC1000


Share on :   Share on Facebook Share on Facebook
SPECIFICATIONS SPECIFICATIONS DESCRIPTION DESCRIPTION

Mains supply

  • 110V/230VAC (-15%, +10%). 50Hz/60Hz.

Operating voltage

  • 20 ~ 28VDC

Power rating

  • Imin=0.45A; Imax.a=1.15A; Imax.b=1.65A

Max. charging current

  • 1A

Max. internal resistance of battery

Quiescent current (full loaded)

  • <0.4A

Approx. Dimensions of the panel (W×H×D)

  • 400×360×104mm

Temperature range:

  • 5°C~ 45°C; Max relative humidity: 95% (40°C ± 2°C, no condensation)

Mains fuse

  • T3.15AL250V

Recommended mains cable

  • Standard/black mains cable, cable size 0.75mm
Manual

SEC1000 Manual