Loading...

4 TO 8 LOOP ADDRESSABLE FIRE ALARM CONTROL PANEL

The SEC3008 control panels are touch-sensitive, addressable fire detection panels, with up to 8 circuits for the SEC3004, each panel supporting up to 324 addressable points, and are designed to meet the requirements of the EN 54-2 & EN 54-4 standards for simple installation, easy operation and easy maintenance..

  • FEATURES:
    • EN54-2& EN54-4 certified by LPCB and Applus.

    • 7.0 inch color touch-sensitive screen LCD, resolution of 800×480.

    • 324 addresses for 1 loop max 8 loops.

    • A maximum of 5000 fire protection zones are supported. More user-friendly Night Mode Time Range Settings.

    • Networkable: CAN bus for interconnection of up to 60 FACPs and Ethernet for up to 254 FACPs.

    • Fire alarm, fault, C&E and operation, each category can store up to 10000 records.

Model: SEC3008/2


Share on :   Share on Facebook Share on Facebook
SPECIFICATIONS SPECIFICATIONS DESCRIPTION DESCRIPTION

Mains fuse

  • T4A250V

Recommended main Cable

  • Standard/black mains cable, cable size 1mm²

Max Battery Supply Current

  • 8A(when the Mains is disconnected

Physical dimensions Battery

  • 450x590x 23mm (24AH or 32Ah) 440×590×180mm(for 18ah)

Approx. weight (without battery)

  • SEC3008(Standard):11Kg ; SEC3008(Deep):13kg

Quiescent current (full loaded)

  • <0.3A

S.C.Out (+, -)

  • 20-28V DC Output Voltage

End of line resistor

  • 10KΩ

F.A Out (+,-)

  • 20-30V DC Output Voltage
Manual

SEC3008 3004 manual

SEC3008 3004 manual