HFA-05ZD

HFA-05 ZD is a selective coded fire alarm control panel and designed to fully supervised and protect the detection and alarm circuit lines. The state-of-the art installation support by functional design and proper maintenance make this equipment highly reliable on all fire emergencies.

FEATURES:

  • Fully supervised sensor and sounder
  • Easy alarm/trouble led distinction: Red for Alarm; Green for Trouble
  • Surface-mounted controls for easy operation: Intermittent tone for Trouble; Continuous beep tone for Alarm

Description

Power Source
             
220 VAC ; 60 Hz
Operating Voltage 24VDC
Power Consumption
                     Standby
                     Full load

11 watts
50 watts
Detection Current Analog ; 50mA
Capacity per Zone
                     Detector
                     Sounder

20 smoke detectors (max.)
200 mA (max.)
Alarm Delay
                     Zone
                     General / Fire Hydrant

15 secs. (default time)
30 secs. (default time)
End-of-Line Resistance
                     Detector
                     Sounder

10k ohms
10k ohms
Alarm Tone Continuous Beep Tone
Trouble Tone Intermittent Tone
Color (Enclosure) White w/ red and black stripe
Dimension of Control Panel 485(H) x 335(W) x 135(D)