Explosion Proof Smoke Detector
Model: DS-1006
Introduction:
        Explosion Proof Smoke Detector is ideally suited to protect large areas with potentially
explosive atmospheres, protection against smoking fires can be provided by this beam.
This includes an infrared transmitter and a receiver both of which are ATEX-certified for use
in Group 2 hazardous areas. There is a separate, safe area, wall-mouted remote low level
control unit to allow adjustment and testing from convenient non-hazardous location. The
product is designed for large enclosures with oil rigs, refineries, ordance store, waste
water treatment plants and similar premises. It provides an early warning of smoldering
smoke generated fires, some of which may not be picked up by flames detectors installed
in many hazardous areas.
   
  HIMMAX Map       SITE Map
Unit Features
                                        Separates Transmitter and Receiver Units certified to EExd
                                        Signal Strength indicating LED's   Product Brochure
                                        Range 33ft. to 330ft. (10m to 100m)
                                        Easy set up and aligment You will find extensive product
                                        Internal test switch information in our PDF Brochures
                                        Conforms to BS5869 Part 5 EExd IIB T6
                                        3 Selectable Alarm Thresholds: 25%, 35% and 50% Click here
                                        Alarm latching or auto reset
                                        Automatic gain control
                                        12 VDC ro 24 VDC operation
                                        Separate alarm and trouble relay contact
                                        Ground Level Control Unit
                                        Alignment by Universal Bracket
Product Specification
OPERATING VOLTAGE : 220 VAC / 50-60Hz   Related Products
POWER INPUT : 11.5 VDC to 24 VDC
STANDBY CURRENT : 8.5 mA @ 24 VDC * Fire Suppression System (SCA-004)
ALARM CURRENT : 16.5 @ 24 VDC * FA 2000 Series
RELAY CONTACTS 2A at 30 VDC; Resistive * Changlong Series (CL-2100 Series)
RESET TIME : 5 Second Maximum * 3 Zone FACP (CFA-203)
START UP TIME : 45 Second; Automaitc * 5 Zone FACP (HFA-505ZD)
OPTICAL WAVELENGTH 880 nm. * J-Net EN54 Control Panel
SENSITIVITY : 25%, 35% and 50% * JuniorV4 Control Panel
FIRE ALARM THRESHOLD : 1.25 dB (25%), 1.87 dB (35%) and 3 dB (50%) * Projected Beam Smoke Detector
BEAM TOLERANCE TO * Explosion Proof Smoke Detector
            MISALIGNMENT AT 35% * Nurse Call Monitoring System
            TRANSMITTER : +/- 1º
            RECEIVER : +/- 4º
TEMPERATURE RATING : -4ºF to 131ºF (-20ºC to +55ºC)
RELATIVE HUMIDITY : 0% to 93% RH non-condensing   Listings
OPERATIONAL RANGE : 33ft. - 330ft. (10 meter - 100 meter)
RFI IMMUNITY : 10 V/m @ KHz-I GHz * ATEX Group 2
FIELD WIRING SIZE : 12 - 24 AWG * SIRA 03ATEX1504
HOUSING (Controller) : Double Pressed Sheet Steel * BS5839
HOUSING (Transmitter / Receiver) : Marine Grade Aluminum Alloy
WEIGHT (kilogram) : Controller: 1.8 kg.; Transmitter/Receiver: 4 kg.
COLOR : Controller: White; Transmitter/Receiver: Red
DIMENSION (mm) Controller : 210 (W) x 265 (H) x 120 (D)
DIMENSION (mm) Transm./Receiver : 120 (W) x 120 (H) x 120(D)

Home  |  About  |  Products  |  Download  |  Services  |  Contact Us  |  Careers