Projected Beam Smoke Detector
Model: DS-1002
Introduction:
        Projected Beam Smoke Detector is designed to be mounted so that the beam will
project between 1ft. (0.305 meter) and 2 ft. (0.61 meter) below and parallel to the ceiling.
Lateral detection may be up to 30 ft. (9.144 meter) either side beam, providing a maximum
total coverage area of up to 19,000 square feet. The system comprises of a transmitter
which projects a modulated infrared light beam to a receiver. The receiver signal is
analyzed by a controller usually located at ground level. If the smoke is present in the path
for more than 8 - 10 seconds, a fire relay is activated in the controller.
   
  HIMMAX Map       SITE Map
Unit Features
                                        Separates Transmitter and Receiver Units certified to EExd
                                        Signal Strength indicating LED's   Product Brochure
                                        Range 33ft. to 330ft. (10m to 100m)
                                        Easy set up and aligment You will find extensive product
                                        Internal test switch information in our PDF Brochures
                                        Calibrated obscuration test filter included
                                        3 Selectable Alarm Thresholds: 25%, 35% and 50% Click here
                                        Alarm latching or auto reset
                                        Automatic gain control
                                        12 VDC ro 24 VDC operation
                                        Separate alarm and trouble relay contact
                                        Ground Level Control Unit
                                        Alignment by Universal Bracket
                                        Microprocessor Controlled
Product Specification
OPERATING VOLTAGE : 220 VAC / 50-60Hz   Related Products
POWER INPUT : 10.2 VDC to 30 VDC
STANDBY CURRENT : 8.5 mA @ 24 VDC * Fire Suppression System (SCA-004)
ALARM CURRENT : 16.5 mA @ 24 VDC * FA 2000 Series
RELAY CONTACTS 2A at 30 VDC; Resistive * Changlong Series (CL-2100 Series)
RESET TIME : 5 Second Maximum * 3 Zone FACP (CFA-203)
START UP TIME : 45 Second; Automaitc * 5 Zone FACP (HFA-505ZD)
OPTICAL WAVELENGTH 880 nm. * J-Net EN54 Control Panel
SENSITIVITY : 25%, 35% and 50% * JuniorV4 Control Panel
FIRE ALARM THRESHOLD : 1.25 dB (25%), 1.87 dB (35%) and 3 dB (50%) * Projected Beam Smoke Detector
BEAM TOLERANCE TO * Explosion Proof Smoke Detector
            MISALIGNMENT AT 35% * Nurse Call Monitoring System
            TRANSMITTER : +/- 1º
            RECEIVER : +/- 4º
TEMPERATURE RATING : -4ºF to 131ºF (-20ºC to +55ºC)
            FOR UL LISTED : 32ºF to 100 ºF (0ºC to 38 ºC)   Listings
PROTECTION : 100 mA FUSE in Control Unit
RELATIVE HUMIDITY : 0% to 93% RH non-condensing * UL Listed
OPERATIONAL RANGE : 33ft. - 330ft. (10 meter - 100 meter) * ULC Listed
RFI IMMUNITY : 10 V/m @ KHz-I GHz * MEA 293-98-E
FIELD WIRING SIZE : 12 - 24 AWG * CSFM 72-60-1508:101
HOUSING (Controller) : Double Pressed Sheet Steel
HOUSING (Transmitter / Receiver) : Marine Grade Aluminum Alloy
WEIGHT (kilogram) : Controller: 1.8 kg.; Transmitter/Receiver: 4 kg.
COLOR : Controller: White; Transmitter/Receiver: Red
DIMENSION (mm) Controller : 210 (W) x 265 (H) x 120 (D)
DIMENSION (mm) Transm./Receiver : 120 (W) x 120 (H) x 120(D)

Home  |  About  |  Products  |  Download  |  Services  |  Contact Us  |  Careers