Junior Mini Repeater
Model: Mini-Rep
Introduction:
        Junior Mini Repeater will provides remote control, system status display and
monitoringfunction for any of GFE's Analogue Addressable Fire Detection Panels. All Fire,
Fault, Test and Disable condition are displayed. User is able control all functions at access
Level's 1, 2 (authorized user level) and 3 (installer / programming level). Compliant with
EN-54 part 2. Display and Control Functions are replicated and shown in the same
manner as on any of GFE's Analogue Addressable Fire Detection Panel. Access to Level 2
and 3 is via a code using the same as programmed for the associated panel.
   
  HIMMAX Map       SITE Map
Unit Features
                                        LED's Test Display Function.
                                        Communicates with the Master Control Panel via RS-422 or RS-485, Fiber Optic.   Product Brochure
                                        Can be supplied from the control panel's Auxiliary Power Output.
You will find extensive product
information in our PDF Brochures
Click here
Product Specification
SUPPLY VOLTAGE : 28 VDC Nominal derived from panel's AUX. Supply O/P   Related Products
SUPPLY CURRENT : 80 mA
CONNECTIONS : + Supply, -Supply plus interface connection * Fire Suppression System (SCA-004)
REPEATER NETWORK : RS-485, Fiber Optical, TCP/IP * FA 2000 Series
4 units maximum when powered from AUX Supply O/P * Changlong Series (CL-2100 Series)
MAXIMUM HUMIDITY : 95% RH Non-Condensing * 3 Zone FACP (CFA-203)
OPERATING TEMPERATURE : 0ºC + 50ºC * 5 Zone FACP (HFA-505ZD)
DIMENSIONS (mm) : 194(W) x 76(H) x 256(D) * J-Net EN54 Control Panel
WEIGHT : 1.5 kg. * JuniorV4 Control Panel